Mô tả
Description
The level electrode NRG 16-11 S is used in conjunction with
level switch NRS 1-50 (de-energizing delay: 15 seconds)
as water-level limiter for steam boilers and (pressurized)
hot-water installations on board of seagoing vessels, mobile
offshore platforms or river boats. Water level limiters switch
off the heating when the water level falls below the set
minimum level (low water).
Technical data
Service pressure
NRG 16-11S: 32 bar g @ 238°C
End connection
Flange, PN 40, DN 50
Materials
Flange 1.0460 C22.8
Measuring electrode 1.4401, X5CrNiMo17-12-2
Electrode insulation Gylon
Terminal box: Polyamid (PA)
Lengths available
500 mm 1000 mm
1500 mm 2000 mm
Cell constant C
0.13 cm-1 with measuring surface extension
0.3 cm-1 without measuring surface extension
Response sensitivity
10 µS/cm at 25°C, cell constant 0.3 cm-1
0,5 µS/cm at 25°C, cell constant 0.13 cm-1
Terminal box
Four-pole connector, cable glands M 16 (PG 9)
Protection
IP 65 to EN 60529
Admissible ambient temperature
Max. 70°C
Weight
Approx. 6.0 kg
Đánh giá