Mô tả
350 ohm strain gage inputPushbutton programming and calibrationConfigwareâ„¢ SW configurableScalable, voltage or current outputsMODbus communication optionPeak and valley detectionTransducer interrupt detectionUL, cUL recognizedCE approvedSpecifications
Performance Characteristics
Instrument type: Digital panel meter
Display: 5 red LED digits 0.5″ (12.7mm) high
2 red LED lights for alarm
1 green LED light for remote configuration
Accuracy: ±0.1%
Normal Mode
Rejection Ratio: 60dB at 50/60Hz
Sampling Time: 100mS
Input
Thermocouple: Types J, K, E, L, N, R, S, T
RTD: Type PT100 (DIN 43760)
Linear Input: 0(4)-20mA and 0(1)-5Vdc and 0(2)-10Vdc
Scaling: ?F or ?C programmable
Alarm Outputs (2)
Alarm Type: Two SPST Form C
Contact Rating: 0.6A @110Vdc, resistive load
0.5A @220Vdc, resistive load
0.3A @110Vdc, inductive load
Alarm Update Time: 100mS
Analog Retransmission Outputs
Type: 0(4)-20mA, 0(1)-5V or 0(2)-10V.
500?, max load
Resolution: ±0.05% of output span maximum
Accuracy: ±0.2% of span
Update Time: 100mS
Serial Communication Interface
Type: Isolated RS-485
Protocol: ModBus/JBus selectable (half duplex)
Baud Rate: 150 – 19200 baud
Format: 8 bits + parity; 8 bits without parity
Parity: Odd / Even
Mechanical & Packaging Characteristics
Termination: Screw terminals on rear with safety covers
Front Panel: IP65/NEMA4-rated with gasket
Operating
Temperatures: 32? – 130?F (0? – 55?C)
Humidity: 5 – 85% relative humidity, non-condensing
Vibration: 10 – 150Hz at a peak of 1G
Approvals & Certifications
CE Mark: EMC standard EN 61326-1 2002
Safety standard EN 61010-1 2001
Agency approvals:
UL: According to UL 3121-1
cUL: According to C22.2 No. 142
C-Tick: Australia
Power Supply (Mains)
Input Power: 85-264 Vac (24V ac/dc available)
Power Consumption: 10W, max
Input Protection: Internal thermistor
Isolation: Reinforced isolation from instrument and
all other I/O circuits
Đánh giá
Chưa có đánh giá nào.